Installation
5.1 Line-side connection
SITOP PSU8200/3800 3ph
50
Manual, 05.2018, C98130-A7638-A1-6-7629
Protection
SITOP PSU8200 3ph
Required line-side protection
6EP3436-8SB00-0AY0
(24 V/20 A)
6EP3446-8SB10-0AY0
(36 V/13 A)
6EP3446-8SB00-0AY0
(48 V/10 A)
6EP3424-8UB00-0AY0
(12 V/20 A)
6EP3436-8UB00-0AY0
(24 V/17 A)
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 6 - 16 A
or
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent trip: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection according to UL489-listed, DIVQ)
6EP1437-3BA10
(24 V/40 A)
3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 10 - 16 A
or
3RV2011-1DA10 circuit breaker, setting of the thermal overcurrent trip: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection according to UL489-listed, DIVQ)
6EP3437-8SB00-0AY0
(24 V/40 A)
6EP3447-8SB00-0AY0
(48 V/20 A)
6EP3437-8UB00-0AY0
(24 V/40 A)
3-pole, coupled miniature circuit breaker 10 - 16 A characteristic C
or
circuit breaker RV2011-1DA10 (setting 3 A)
or
3RV2711-1DD10 (UL489-listed, DIVQ)
The protective conductor of the line supply must be connected at the PE terminal.
NOTICE
Country-specific regulations must be observed when installing.
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...