Safety, approvals, EMC
7.2 Test voltage
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
87
Table 7- 2
Test voltage for 6EP1437-3BA10
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2200 V DC
700 V DC
60 s
3000 V AC
1500 V AC
500 V AC
Production test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
Table 7- 3
Test voltage for 6EP3437-8SB00-0AY0, 6EP3447-8SB00-0AY0 and 6EP3437-8UB00-0AY0
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2540 V DC
850 V DC
60 s
3000 V AC
1700 V AC
600 V AC
Production test
1 s
2540 V DC
2540 V DC
850 V DC
1 s
1700 V AC
1700 V AC
600 V AC
Field test
1 s
2540 V DC
2540 V DC
850 V DC
1 s
1700 V AC
1700 V AC
600 V AC
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...