Description, device design, dimension drawing
2.5 Change-over switch
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
19
For 6EP3437-8UB00-0AY0 (24 V/40 A)
Switch
ON
OFF
A
influences the output
characteristic in the
load range
Parallel operation:
"Soft" characteristic curve (see Figure 6-20 Output
characteristic 6EP3437-8UB00-0AY0 parallel opera-
tion (B OFF) (Page 67)) for the parallel operation of
two or more devices: The output voltage falls with
increasing output current.
This means that for full output current the highest
output voltage can normally no longer be attained.
Single operation:
delivery condition
"Hard" characteristic curve (see Figure 6-
11 Output characteristic 6EP3437-
8UB00-0AY0 single operation (B OFF)
(Page 64)) for normal operation (single
operation): The output voltage is inde-
pendent of the output current.
B
is used to switch over
the output current
Rated current:
I
out rated
= 30 A, no latching shutdown
see Figure 6-29 Output characteristic 6EP3437-
8UB00-0AY0 single operation (Page 70)
Rated current:
delivery condition
I
out rated
= 40 A, no latching shutdown
Note
Selector switches may only be activated when the device is switched off.
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...