Safety, approvals, EMC
7.2 Test voltage
SITOP PSU8200/3800 3ph
86
Manual, 05.2018, C98130-A7638-A1-6-7629
7.2
Test voltage
Figure 7-1
Test voltage diagram
Only the manufacturer can perform the type test and production test; users can also perform
the field test.
Preconditions for performing the field test:
Tests (A) & (B)
●
Connect the input terminals with one another
●
Connect the output terminals, signaling contact, remote and PE with one another
Test (C)
●
Connect the output terminals and signaling contact with one another and measure with
respect to PE
Table 7- 1
Test voltage for 6EP3436-8SB00-0AY0, 6EP3446-8SB10-0AY0, 6EP3446-8SB00-0AY0, 6EP3424-8UB00-
0AY0 and 6EP3436-8UB00-0AY0
Test time
Prim ↔ sec (A)
Prim ↔ PE (B)
Sec ↔ PE (C)
Type test
60 s
4200 V DC
2200 V DC
700 V DC
60 s
3000 V AC
1500 V AC
500 V AC
Production test
1 s
4200 V DC
4200 V DC
500 V DC
1 s
3000 V AC
3000 V AC
350 V AC
Field test
1 s
2200 V DC
2200 V DC
500 V DC
1 s
1500 V AC
1500 V AC
350 V AC
Note:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
Содержание SITOP PSU3800 12 V/20 A
Страница 6: ...Overview SITOP PSU8200 3800 3ph 6 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 52: ...Installation 5 2 Output side connection SITOP PSU8200 3800 3ph 52 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 84: ...Technical data 6 9 Dimension drawing SITOP PSU8200 3800 3ph 84 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 90: ...Safety approvals EMC 7 4 EMC SITOP PSU8200 3800 3ph 90 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 104: ...Applications 9 7 Battery charging with SITOP PSU3800 SITOP PSU8200 3800 3ph 104 Manual 05 2018 C98130 A7638 A1 6 7629 ...
Страница 106: ...Environment SITOP PSU8200 3800 3ph 106 Manual 05 2018 C98130 A7638 A1 6 7629 ...