Mounting and dismantling
3.4 Connecting the 3RW5 HMI
SIRIUS 3RW50 soft starter
56
Manual, 09/2019, A5E35628455002A/RS-AA/001
3.4.2
Installing the Standard 3RW5 HMI into the control cabinet door
Requirements
●
Note the mounting positions, minimum clearances and ambient conditions stated on the
data sheet.
●
3RW5 HMI Standard (accessories)
●
HMI connecting cable (accessory) of suitable length connected to the soft starter
(Page 55)
●
Cutout of suitable size in the control cabinet door
●
Device depth of the 3RW5 HMI Standard:
–
Total depth: 32 mm
–
Embedded depth: 29 mm
●
Permissible wall thickness of the cabinet door:
–
Without IP65 door mounting kit: 1.5 to 3.0 mm
–
With IP65 door mounting kit: 1.0 to 7.0 mm
For using door mounting kit IP65:
●
IP65 door mounting kit (accessory)
The fixing brackets with marking "001" are intended for a 3RW5 HMI Standard.
●
Screwdriver PZ2
Procedure without door mounting kit IP65
Place the 3RW5 HMI Standard in the cutout of the control cabinet door
①
. Ensure that the
3RW5 HMI Standard engages audibly in the 4 fixtures
②
.
Содержание SIRIUS 3RW50
Страница 8: ...Table of contents SIRIUS 3RW50 soft starter 8 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 38: ...Description 1 13 Support Request SIRIUS 3RW50 soft starter 38 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 90: ...Connecting 4 11 COM connection cable SIRIUS 3RW50 soft starter 90 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 160: ...Functions 7 12 3RW5 HMI High Feature SIRIUS 3RW50 soft starter 160 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 184: ...Messages and diagnosis 8 11 Logbooks SIRIUS 3RW50 soft starter 184 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 202: ...Circuit diagrams 12 1 CAx data SIRIUS 3RW50 soft starter 202 Manual 09 2019 A5E35628455002A RS AA 001 ...