Description
1.5 Operating modes and master control function
SIRIUS 3RW50 soft starter
18
Manual, 09/2019, A5E35628455002A/RS-AA/001
"Automatic" mode
Receive master control function
The "Automatic" mode receives the master control function from the "Manual - bus" or
"Manual - local" mode as follows:
●
Command in SIRIUS Soft Starter ES (TIA Portal) Premium (fieldbus)
●
Action "LOCAL / REMOTE" on the 3RW5 HMI
●
Command in SIRIUS Soft Starter ES (TIA Portal)
(local interface on the 3RW5 HMI High Feature)
Assume master control
By disabling the "Manual operation local - input controlled" bit in the process image output
(PIQ) or in the data table "Process image output (PIQ)" (depending on the
3RW5 communication module), the "Automatic" mode receives the master control function
from the Input IN.
Relinquish master control
By enabling the "Manual operation local - input controlled" bit in the process image output
(PIQ) or in the data table "Process image output (PIQ)" (depending on the
3RW5 communication module) the "Automatic" mode gives up the master control function to
the Input IN.
Revocation of the master control by other control sources
In the "Automatic" mode, the master control function can be withdrawn from any control
source.
Operating mode "manual - bus"
Assume master control
SIRIUS Soft Starter ES (TIA Portal) Premium actively assumes the master control function
from the "Automatic" mode in the event of a corresponding command.
Relinquish master control
SIRIUS Soft Starter ES (TIA Portal) Premium actively passes on the master control function
to the "Automatic" mode in the event of a corresponding command.
Revocation of the master control by other control sources
The master control function is withdrawn from the operating mode "manual - bus" by the
operating mode "manual - local" as follows:
●
Activation of the "Manual operation local - input controlled" bit in the process image
output (PIQ) or in the data table "Process image output (PIQ)"
(depending on the 3RW5 communication module)
●
Action "LOCAL / REMOTE" on the 3RW5 HMI
●
Command in SIRIUS Soft Starter ES (TIA Portal)
(local interface on the 3RW5 HMI High Feature)
Содержание SIRIUS 3RW50
Страница 8: ...Table of contents SIRIUS 3RW50 soft starter 8 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 38: ...Description 1 13 Support Request SIRIUS 3RW50 soft starter 38 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 90: ...Connecting 4 11 COM connection cable SIRIUS 3RW50 soft starter 90 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 160: ...Functions 7 12 3RW5 HMI High Feature SIRIUS 3RW50 soft starter 160 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 184: ...Messages and diagnosis 8 11 Logbooks SIRIUS 3RW50 soft starter 184 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 202: ...Circuit diagrams 12 1 CAx data SIRIUS 3RW50 soft starter 202 Manual 09 2019 A5E35628455002A RS AA 001 ...