Maintenance and service
9.4 Restoring factory setting
SIRIUS 3RW50 soft starter
192
Manual, 09/2019, A5E35628455002A/RS-AA/001
9.4.4
Restoring the factory settings with the MODE and RESET / TEST keys
Requirements
●
Make sure that the motor is switched off and you do not start the motor while restoring the
factory settings.
To ensure the quickest and most fault-free restoration of the factory setting, it is
recommended that you disconnect the main voltage at the 3RW50 soft starter.
●
The 3RW5 communication module must be isolated from the 3RW50 soft starter.
Procedure
1.
Start the restoration of the factory settings by pressing the MODE key longer than 2 s
until the STATE / OVERLOAD LED flickers green.
Press and hold the MODE key.
2.
Simultaneously press the RESET / TEST key down for at least 10 s.
After 2 s, the STATE / OVERLOAD LED begins to illuminate red.
After 10 s the STATE / OVERLOAD LED goes out and switches back to displaying the
motor operating state (e.g. flashing yellow if there is no supply voltage).
3.
Release the MODE and RESET / TEST keys.
Result
The factory setting of the 3RW50 soft starter has been restored.
Note the effects of the factory settings described in Chapter Effects of the factory setting
(Page 189).
Содержание SIRIUS 3RW50
Страница 8: ...Table of contents SIRIUS 3RW50 soft starter 8 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 38: ...Description 1 13 Support Request SIRIUS 3RW50 soft starter 38 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 90: ...Connecting 4 11 COM connection cable SIRIUS 3RW50 soft starter 90 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 160: ...Functions 7 12 3RW5 HMI High Feature SIRIUS 3RW50 soft starter 160 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 184: ...Messages and diagnosis 8 11 Logbooks SIRIUS 3RW50 soft starter 184 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 202: ...Circuit diagrams 12 1 CAx data SIRIUS 3RW50 soft starter 202 Manual 09 2019 A5E35628455002A RS AA 001 ...