Messages and diagnosis
8.10 Self-test (user-test)
SIRIUS 3RW50 soft starter
180
Manual, 09/2019, A5E35628455002A/RS-AA/001
Test result
The test results are provided in the following tables. If the 3RW5 soft starter does not
respond as shown in the tables below during the function test, check the external
connections, their function, and the wiring. If the error persists even though the connections
are correct, the 3RW5 soft starter must be replaced.
If a 3RW5 HMI is connected to the 3RW5 soft starter, the 3RW5 indicates "Motor overload
tripping" when it passes the function test. If the 3RW5 soft starter does not pass the function
test, the 3RW5 HMI indicates a device error.
LED test
LED
Display of test result
pass
fail
"RN"
Lights up green
Off
"ER"
Lights up red
Off
"MT"
Lights up yellow
Off
"STATE / OVERLOAD"
Lights up yellow
Off
"RESET MODE"
Lights up green
Off
"SOFT TORQUE"
Lights up green
Off
Содержание SIRIUS 3RW50
Страница 8: ...Table of contents SIRIUS 3RW50 soft starter 8 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 38: ...Description 1 13 Support Request SIRIUS 3RW50 soft starter 38 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 90: ...Connecting 4 11 COM connection cable SIRIUS 3RW50 soft starter 90 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 160: ...Functions 7 12 3RW5 HMI High Feature SIRIUS 3RW50 soft starter 160 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 184: ...Messages and diagnosis 8 11 Logbooks SIRIUS 3RW50 soft starter 184 Manual 09 2019 A5E35628455002A RS AA 001 ...
Страница 202: ...Circuit diagrams 12 1 CAx data SIRIUS 3RW50 soft starter 202 Manual 09 2019 A5E35628455002A RS AA 001 ...