Parameter assignment
5.5 Setting RESET MODE and Soft Torque
SIRIUS 3RW50 soft starter
Manual, 09/2019, A5E35628455002A/RS-AA/001
97
RESET MODE
Note that the setting of the RESET MODE (Page 98) only has an effect on the
acknowledgment response of the motor overload protection.
You will find more information in Chapter Faults and remedial actions of the
3RW50 soft starter (Page 168) with the comment "Depends on parameter RESET MODE".
Note
ATEX / IECEx applications
Note that the "Auto RESET" setting is not permissible when operating motors in hazardous
areas.
RESET MODE LED
Set RESET MODE
Off
Manual RESET
Flashes green
Remote RESET
Lights up green
Auto RESET
Soft torque
For more information, see Chapter Soft torque (Page 130).
SOFT TORQUE LED
Set soft torque
Off
Off
Lights up green
On