Commissioning
5.5 Factory settings for the Inverter
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
67
5.5
Factory settings for the Inverter
Default command and setpoint sources
Inverters used in automation solutions have the appropriate fieldbus interfaces. These
Inverters are preset in the factory so that the appropriate control and status signals can be
exchanged using the fieldbus interface.
Table 5- 1
Command and setpoint sources
Parameter
Description
P0700 = 6
Select the command source
Fieldbus
P1000 = 3
Select the setpoint source
Fixed frequencies
Table 5- 2
Factory setting of additional important parameters
Parameter Factory setting Meaning of the factory setting
Function
Access
level
P0003
1
Access to the most frequently used
parameters
Selecting the user access level
1
P0004
0
All parameters are displayed
Parameter filter: filters parameters in ac-
cordance with the functionality
1
P0010
0
Ready to be entered
Commissioning parameter
1
P0100
0
Europe [50 Hz]
Frequency of the regional supply network
•
IEC, Europe
•
NEMA, North America
1
P0300
1
Induction motor
Select the motor type (induction motors /
synchronous motor)
2
P0304
400
[V]
Rated motor voltage
(in accordance with rating plate in V)
1
P0305
depends on
the
Power Module
[A]
Rated motor current
(in accordance with rating plate in A)
1
P0307
depends on
the
Power Module
[kW/hp]
Rated motor output
(in accordance with the rating plate in
kW/hp)
1
P0308
0
[cos phi]
Rated motor power factor (in accordance
with rating plate in cos 'phi') when P0100 =
1.2, then P0308 is irrelevant
1
P0309
0
[%]
Rated motor efficiency (in accordance with
rating plate in %) when P0100 = 0, then
P0309 is irrelevant
1
P0310
50
[Hz]
Rated motor frequency
(in accordance with rating plate in Hz)
1
P0311
1395
[rpm]
Rated motor speed
(in accordance with rating plate in rpm)
1
Содержание SINAMICS G110D
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents SINAMICS G110D 8 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Страница 208: ...Messages and fault codes 8 2 LED States SINAMICS G110D 208 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Страница 223: ......
Страница 224: ......