Commissioning
5.5 Factory settings for the Inverter
SINAMICS G110D
68
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Parameter Factory setting Meaning of the factory setting
Function
Access
level
P0335
0
Non-ventilated: Shaft-mounted fan
in the motor
Motor cooling (specify the motor cooling
system)
2
P0625
20
°C
Ambient temperature of motor
3
P0640
200
[%]
Motor overload factor (entered in % referred
to P0305)
2
P0700
6
6 (default setting)
Select the command source
1
P0727
0
DI0: On / off
DI1: Direction reversal
Control response when the motor starts
(start, stop, reverse)
3
P0970
0
Blocked
Restore factory settings
1
P1000
3
Fixed frequencies
Select the source of the frequency setpoint
(setpoint input)
1
P1080
0
[Hz]
Minimum frequency
1
P1082
50
[Hz]
Maximum frequency
1
P1120
10
[s]
Ramp-up time
1
P1121
10
[s]
Ramp-down time
1
P1300
0
V/f control with linear characteristic Control mode
2
P3900
0
No quick commissioning
Completes the quick commissioning.