Functions
6.4 Setpoint sources
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
107
6.4.3
Using a motorized potentiometer as a setpoint source
Frequency setpoint using motorized potentiometer (MOP) (when P1000 = 1 -> P1031)
The 'motorized potentiometer' function simulates an electromechanical potentiometer for
entering setpoints. The value of the motorized potentiometer (MOP) can be set by means of
the "up" and "down" control commands.
Table 6- 18 Example: Implementing the motorized potentiometer using the Operator Panel keys
Parameter Description
P1000 = 1
1: MOP setpoint
P1031 = 0
Setpoint memory of the MOP
The last motorized potentiometer setpoint that was active prior to the OFF command
or shutdown can be saved.
0: MOP setpoint is not saved (factory setting)
1: MOP setpoint is saved in P1040
P1032 = 1
Disable opposite direction of the MOP
0: Reverse direction of rotation is permitted
1: Reverse direction of rotation is locked (factory setting)
P1040 = 5
Setpoint of the MOP
Determines the setpoint [Hz] of the motorized potentiometer (MOP). Factory setting 5
Hz
P2000 = 50
Reference frequency (Hz);
An output value of the MOP of 100 % corresponds to the frequency setpoint from
P2000. P2000 should be changed, if a maximum frequency greater than 50 Hz is
required.
Table 6- 19 Example: Implementing a motorized potentiometer using digital inputs
Parameters Description
P0700 = 2
2: Digital inputs P0701…P0704 (DI x ON/OFF1; DI y "up" and DI z "down")
P0701 = 1
1: ON/OFF1
P0702 = 13
13: MOP "up"
P0703 = 14 14: MOP "down"
P1000 = 1
1: MOP setpoint
P1031 = 0
Setpoint memory of the MOP
The last motorized potentiometer setpoint that was active prior to the OFF command
or shutdown can be saved.
0: MOP setpoint is not saved (factory setting)
1: MOP setpoint is saved in P1040
P1032 = 1
Disable opposite direction of the MOP
0: Reverse direction of rotation is permitted
1: Reverse direction of rotation is locked (factory setting)
P1040 = 5
Setpoint of the MOP
Determines the setpoint [Hz] of the motorized potentiometer (MOP); factory setting, 5
Hz
P2000 = 50
Reference frequency (Hz);
An output value of the MOP of 100 % corresponds to the frequency setpoint from
P2000. P2000 should be changed, if a maximum frequency greater than 50 Hz is
required.