Functions
6.11 Operation in fieldbus systems
SINAMICS G110D
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
163
Image 6-25 AS-i master - set button
The second method is to use the AS-i programming unit to manually set the address of both
the Inverter slave nodes.
Connect the AS-i programming unit to the Inverter (as shown below). The AS-i address
connection is underneath the Control Module cover.
Once the AS-i programming unit is connected, turn the main dial to "ADDR", the screen will
then display an AS-i slave address of '1'. Using the 'up' and 'down' cursor keys, navigate to
the required address. Press the return button (on the far right) to confirm and enter the
address into the slaves memory. Repeat this process for the second slave address required
by the Inverter.
Image 6-26 Setting the address on the Inverter