Functions
6.11 Operation in fieldbus systems
SINAMICS G110D
178
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Error code Description
Errors set by task
101
Parameter deactivated at the moment; parameter has no function in the present
state of the drive converter.
1 to 15
102
Reply does not fit into buffer; depends on the number of PKW and the maximum net
data length of the drive. Dependent on the number of PKW and the maximum net
data length in the drive.
104
Parameter value not permissible. The parameter value does not have an assigned
function in the drive converter or cannot be accepted at the instant of the change for
internal reasons (although it is within the limits) or the expert level has not been set
or the value is not within the selection list. [PKW1 = 104, PKW2 = next value]
2, 3, 7, 8 or 11 to 14
105
Parameter is indexed
106
Request is not implemented/task not supported
5,10 or 15
109
PKW request access timeout or number of retries is exceeded or wait for response
from CPU side.
110
Parameter value cannot be changed (because parameter is Locked).
200
Modified lower limit exceeded.
2, 3, 7, 8 or 11 to 15
201
Modified upper limit exceeded.
2, 3, 7, 8 or 11 to 15
202
No display on the operator panel. Parameter must be hidden on the operator panel. 1 to 15
203
No display on the operator panel. Parameter must be hidden on the operator panel. 1 to 15
204
The available access authorization (i.e. level) does not cover modification of param-
eter (similar to 11 but used in combination with the secret password parameter).
1 to 15
210 - 214
Operator panel error codes;
210 = insufficient storage space in operator panel
211 = storage block cannot be found
212 = invalid block type for operation
213 = error in command arguments
214 = special operation failed
300
Array elements differ.
IND components
The IND word contains two pieces of information. The first is the page number of the
parameter to be accessed. The page is stored in bits 10-15 of the IND word in reverse
format, i.e. bit 15 is the least significant bit of the page number. As an example, consider the
following:
Parameter 3900:3900 = 1 x 2000 + 1900PP = binary 100000 = 1 PNU = 1900
Parameter 4100:4100 = 2 x 2000 + 100PP = binary 010000 = 2 PNU = 100
Image 6-36 IND component structure
Содержание SINAMICS G110D
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents SINAMICS G110D 8 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Страница 208: ...Messages and fault codes 8 2 LED States SINAMICS G110D 208 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Страница 223: ......
Страница 224: ......