Connection
4.10 Using the AS-i Programmer
SINAMICS G110D
60
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
Changing existing addresses of the AS-i slaves
If the allocated addresses used two different numbers, for example, 10A and 11A, then if one
of the slave addresses is reset to 0 the other slave is not affected.
If the allocated addresses use the same number, for example, 20A and 20B, then if one
slave addresses is reset to 0, then both slaves numbers will be reset to 0.
Modifying an existing address of a single slave within the Inverter will not affect the address
of the other slave.
To change an existing address of a slave, the following procedure should be performed:
1. Plug the AS-i Programmer into the addressing socket of the Inverter
2. Turn the dial on the Programmer to the ADDR position. The display
will indicate that this mode has been selected.
3. Press the
button; the screen will display uSE and the number
of the lower addressed slave.
The existing slave addresses are shown at the bottom of the dis-
play.
4. Press the
and
buttons to select the slave address number to be changed.
5. Press the
button; the display now shows SEt.
The selected number will begin to flash.
6. Press the
and
buttons to select the new slave address
number.
7. Press the
button to confirm the new address.
ProG is displayed briefly followed by confirmation of the address
change.
Содержание SINAMICS G110D
Страница 1: ......
Страница 2: ......
Страница 8: ...Table of contents SINAMICS G110D 8 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Страница 208: ...Messages and fault codes 8 2 LED States SINAMICS G110D 208 Operating Instructions 07 2016 FW V3 63 A5E36768472B AB ...
Страница 223: ......
Страница 224: ......