Functions
6.7 Motor control
SINAMICS G110D
120
Operating Instructions, 07/2016, FW V3.63, A5E36768472B AB
6.7.2
V/f control with parabolic characteristic
Note
V/f control with a parabolic characteristic must not be used in applications in which a high
torque is required at low speeds.
Table 6- 31 Setting the control type
Parameter Description
P0003 = 2
Extended access
P1300 = 2
Control type: V/f control with parabolic characteristic
6.7.3
Typical applications for V/f control
V/f control is perfectly suitable for almost any application in which the speed of induction
motors is to be changed. Examples of typical applications for V/f control include:
●
Pumps
●
Fans
●
Compressors
●
Horizontal conveyors
Basic properties of V/f control
V/f control sets the voltage at the motor terminals on the basis of the specified speed
setpoint. The relationship between the speed setpoint and stator voltage is calculated using
characteristic curves. The inverter provides the two most important characteristics (linear
and square-law). User-defined characteristic curves are also supported.
V/f control is not a high-precision method of controling the speed of the motor. The speed
setpoint and the speed of the motor shaft are always slightly different. The deviation
depends on the motor load. If the connected motor is loaded with the rated torque, the motor
speed is below the speed setpoint by the amount of the rated slip. If the load is driving the
motor (i.e. the motor is operating as a generator), the motor speed is above the speed
setpoint.