01.04
Connectors and binectors
SIEMENS AG 6SG7000-0BA76
12-3
SIMOTRAS HD Operating Instructions
Connector Description
Normalization
Function
diag., Sheet
K0044
Actual position value, number of zero markers
1
=
∧
1
G145
KK0046
Actual position value
[SW 1.9 and later]
Actual position value extended in the software to a 32-bit value
(value range: 8000 0000H to 7FFF FFFFH or –2
31
to +2
31
-1 )
1
=
∧
1
G145
KK0047
Deceleration distance
[SW 1.9 and later]
When setpoint 0 is applied to the ramp-function generator input, the speed
setpoint at the generator output is reduced to zero according to the current
settings for ramp-down and transition roundings.
This double-word connector specifies the requisite deceleration distance as
the number of increments of the pulse encoder (defined in parameters P140
ff.).
This deceleration distance calculation is correct only on the condition that
the parameterized ramp-down time and transition roundings do not change
during the braking operation.
1
=
∧
1
G136
K0048
Actual speed value from pulse encoder in rpm
[SW 2.0 and later] 1
=
∧
1 rpm
G145
Heatsink temperature
K0050
Heatsink temperature
16384
=
∧
100°C
Temperature sensor inputs
K0051 or K0052 is always set to 0 when a PTC thermistor or no temperature sensor is connected (P490.x
≠
1).
K0051
Motor temperature 1 (from sensor to terminal 22 / 23)
16384
=
∧
100°C
G185
K0052
Motor temperature 2 (from sensor to terminal 204 / 205)
16384
=
∧
100°C
G185
Closed-loop current control, auto-reversing stage, gating unit
K0100
Firing angle
16384
=
∧
0°
0
=
∧
90°
-16384
=
∧
180°
G163
K0101
Firing angle before limitation
16384
=
∧
0°
0
=
∧
90°
-16384
=
∧
180°
G163
K0102
Precontrol value + current controller output
(gating unit input)
16384
=
∧
0°
0
=
∧
90°
-16384
=
∧
180°
G162
K0103
pulses
firing
2
between
time
flow
current
of
duration
100%
∗
[SW 2.0 and later] 16384
=
∧
100%
G162
K0105
Code of triggered thyristor pair in a thyristor bridge for switching through the
corresponding line phase:
0 UV
2 UW
4 VW
6 VU
8 WU
10 WV
1
=
∧
1
K0106
Requested torque direction
0 = No torque direction
1 = Torque direction I
2 = Torque direction II
G163
K0107
Internal actual current value, signed, averaged over the last 6 current peaks
in each case, normalized to rated motor current
[SW 1.9 and later]
16384
=
∧
100% of P100
G162
K0108
RMS value of stator current, averaged over one line period
16384
=
∧
100%
K0109
Internal signed actual current value, averaged over the last 6 current peaks
in each case
16384
=
∧
100%
G162
K0110
Current controller output
16384
=
∧
100%
G162
K0111
Current controller output, P component
16384
=
∧
100%
G162
K0112
Current controller output, I component
16384
=
∧
100%
G162
K0113
Current controller, setpoint/actual value deviation
16384
=
∧
100%
G162
K0114
Internal signed actual current value, averaged over one firing cycle
16384
=
∧
100%
G162
K0115
Current controller actual value
16384
=
∧
100%
G162
K0116
Absolute value of internal actual current
16384
=
∧
100%
G162
Содержание SIMOTRAS 6SG7050
Страница 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 570: ...Connectors and binectors 01 04 12 60 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 590: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 603: ......