01.04
Parameter list
SIEMENS AG 6SG7000-0BA76
11-127
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
U544
(2544)
*
S00
(B180...
B189)
Source for variable negative Limit
[SW 1.8 and later]
The content of the selected connector acts as the negative limit for the
output of the technology controller after multiplication with U510.
0 = Connector K0000
1 = Connector K0001
etc.
i001: PI
controller
1
i002: PI
controller
2
...
i010: PI
controller
10
Note:
If the content of the selected connector has a positive value, this causes a
positive minimum value at the output of this limiter stage.
Note:
Connectors K9306 to K9396 contain for PI controllers 1 to 10 the positive
limitation values formed by U542 and U543 with an inverted sign. In this
way it is possible to set the negative limitation symmetrically to the positive
limitation by setting U544= 9306 to 9396 and U545=100.0.
All connector
numbers
1
Ind: 10
FS=
i001: 9306
i002: 9316
i003: 9326
i004: 9336
i005: 9346
i006: 9356
i007: 9366
i008: 9376
i009: 9386
i010: 9396
Type: L2
P052 = 3
P051 = 40
Offline
U545
(2545)
S00
(B180...
B189)
Negative limit for the output of the PI controller
[SW 1.8 and later]
See also U544
0.0 to 199.9
[%]
0.1
Ind: 10
FS=100.0
Type: O2
P052 = 3
P051 = 40
Online
11.70 Closed-loop control elements
Derivative / delay elements
[SW 1.8 and later}
FB 270 to FB 279
U550
(2550)
*
S00
(B156)
(B157)
(B158)
Source for input quantity
[SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001: Input quantity derivative/delay element 1
(FB 270)
i002: Input quantity derivative/delay element 2
(FB 271)
i003: Input quantity derivative/delay element 3
(FB 272)
i004: Input quantity derivative/delay element 4
(FB 273)
i005: Input quantity derivative/delay element 5
(FB 274)
i006: Input quantity derivative/delay element 6
(FB 275)
i007: Input quantity derivative/delay element 7
(FB 276)
i008: Input quantity derivative/delay element 8
(FB 277)
i009: Input quantity derivative/delay element 9
(FB 278)
i010: Input quantity derivative/delay element 10
(FB 279)
All connector
numbers
1
Ind: 10
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
U551
(2551)
*
S00
(B156)
(B157)
(B158)
Source for multiplier for derivative-action time
[SW 1.8 and later]
0 = Connector K0000
1 = Connector K0001
etc.
i001: Multiplier
derivative/delay element 1
(FB 270)
i002: Multiplier
derivative/delay element 2
(FB 271)
I003: Multiplier
derivative/delay element 3
(FB 272)
i004: Multiplier
derivative/delay element 4
(FB 273)
i005: Multiplier
derivative/delay element 5
(FB 274)
i006: Multiplier
derivative/delay element 6
(FB 275)
i007: Multiplier
derivative/delay element 7
(FB 276)
i008: Multiplier
derivative/delay element 8
(FB 277)
i009: Multiplier
derivative/delay element 9
(FB 278)
i010: Multiplier
derivative/delay element 10
(FB 279)
All connector
numbers
1
Ind: 10
FS=1
Type: L2
P052 = 3
P051 = 40
Offline
Содержание SIMOTRAS 6SG7050
Страница 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 570: ...Connectors and binectors 01 04 12 60 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 590: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 603: ......