01.04
Parameter list
SIEMENS AG 6SG7000-0BA76
11-29
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
P361
FDS
Delay time for the undervoltage monitoring
[SW 1.7 and later]
Activation of the fault message F006 (line undervoltage) is delayed by the
time that can be set in this parameter. During this delay time firing pulses
are output!
Another time which is parameterized for automatic restarting (P086) only
begins after the time set here has elapsed.
0 to 60000
[ms]
1ms
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
P362
FDS
Delay time for the overvoltage monitoring
[SW 1.7 and later]
Activation of the fault message F007 (line overvoltage) is delayed by the
time that can be set in this parameter. During this delay time firing pulses
are output!
Another time which is parameterized for automatic restarting (P086) only
begins after the time set here has elapsed.
0 to 60000
[ms]
1ms
Ind: 4
FS=10000
Type: O2
P052 = 3
P051 = 40
Online
P363
FDS
Threshold for the minimum line frequency
[SW 1.8 and later]
If the line frequency falls below the value set here and does not rise above
it again within the "restart" time set in P086, the fault message F008 is
activated. As long as the line frequency is below the value set here, the
drive is kept in operating state o4.
[values < 45.0 Hz can be set in SW 1.9 and later]
CAUTION
Operation in the extended frequency range between 23 Hz and 110 Hz
is available on request.
23.0 to 60.0
[Hz]
0.1 Hz
Ind: 4
FS=45.0
Type: O2
P052 = 3
P051 = 40
Online
P364
FDS
Threshold for the maximum line frequency
[SW 1.8 and later]
If the line frequency rises above the value set here and does not fall below
it again within the "restart" time set in P086, the fault message F009 is
activated. As long as the line frequency is above the value set here, the
drive is kept in operating state o4.
CAUTION
Operation in the extended frequency range between 23 Hz and 110 Hz
is available on request.
50.0 to 110.0
[Hz]
0.1 Hz
Ind: 4
FS=65.0
Type: O2
P052 = 3
P051 = 40
Online
11.16 Setting values for limit-value monitors
(see also Section 8, Sheet G187 and G188)
n < nmin
signal
P370
FDS
(G188)
Speed threshold nmin
Speed threshold for n < nmin limit-value monitor.
Note:
This threshold also affects the sequence of control operations at
”shutdown”, ”fast stop”, cancellation of ”Inch” or ”Crawl” command (see
section 9).
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=5.00
Type: O2
P052 = 3
P051 = 40
Online
P371
FDS
(G188)
Hysteresis for n < nmin signal
This value is added to the response threshold if n < nmin is active.
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=0.50
Type: O2
P052 = 3
P051 = 40
Online
n < ncomp. signal
P373
FDS
(G187)
Speed threshold ncomp.
Speed threshold for n < ncomp. signal
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=100.00
Type: O2
P052 = 3
P051 = 40
Online
P374
FDS
(G187)
Hysteresis for < ncomp. signal (n < ncomp. signal)
This value is added to the response threshold if n < ncomp.
is active.
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=3.00
Type: O2
P052 = 3
P051 = 40
Online
Содержание SIMOTRAS 6SG7050
Страница 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 570: ...Connectors and binectors 01 04 12 60 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 590: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 603: ......