Parameter list
01.04
11-30
SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
PNU
Description
Value range
[Unit]
No. indices See
Change
P375
FDS
(G187)
OFF delay for n < ncomp. signal
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=3.0
Type: O2
P052 = 3
P051 = 40
Online
Setpoint/actual value deviation 2
P376
FDS
(G187)
Permissible setpoint/actual value deviation 2
[SW 1.9 and later]
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FD=3.00
Type: O2
P052 = 3
P051 = 40
Online
P377
FDS
(G187)
Hysteresis for setpoint/actual value deviation 2 signal
[SW 1.9 and later]
This value is added to the response threshold if a setpoint/actual value
deviation signal is active
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
P378
FDS
(G187)
Response delay for setpoint/actual value deviation signal 2
[SW 1.9 and later]
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=3.0
Type: O2
P052 = 3
P051 = 40
Online
Overspeed
P380
FDS
(G188)
Maximum speed in positive direction of rotation
0.0 to 199.9
[%]
0.1% of maximum
speed
Ind: 4
FS=120.0
Type: O2
P052 = 3
P051 = 40
Online
P381
FDS
(G188)
Maximum speed in negative direction of rotation
-199.9 to 0.0
[%]
0.1% of maximum
speed
Ind: 4
FS=-120.0
Type: I2
P052 = 3
P051 = 40
Online
Setpoint/actual value deviation
P387
FDS
(G187)
OFF delay
If the system leaves the state “Setpoint in the controlled range“, the system
waits for the time set here until the setpoint/actual value comparison for the
“setpoint/actual deviation“ signal (status word 1 bit 8)becomes active again
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=2.0
Type: O2
P052 = 3
P051 = 40
Online
P388
FDS
(G187)
Permissible deviation between setpoint and actual value
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=5.00
Type: O2
P052 = 3
P051 = 40
Online
P389
FDS
(G187)
Hysteresis for setpoint/actual value deviation signal
This value is added to the response threshold if a setpoint/actual value
deviation signal is active
0.00 to 199.99
[%]
0.01% of maximum
speed
Ind: 4
FS=1.00
Type: O2
P052 = 3
P051 = 40
Online
P390
FDS
(G187)
Response delay for setpoint/actual value deviation signal
0.0 to 100.0
[s]
0.1s
Ind: 4
FS=1.0
Type: O2
P052 = 3
P051 = 40
Online
11.17 Settable fixed values
Function: The value set in the parameter is applied to the specified connector
P401
FDS
(G120)
K401 fixed value
is applied to connector K0401
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=60.00
Type: I2
P052 = 3
P051 = 40
Online
P402
FDS
(G120)
K402 fixed value
is applied to connector K0402
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P403
FDS
(G120)
K403 fixed value
is applied to connector K0403
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P404
FDS
(G120)
K404 fixed value
is applied to connector K0404
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P405
FDS
(G120)
K405 fixed value
is applied to connector K0405
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
P406
FDS
(G120)
K406 fixed value
is applied to connector K0406
-199.99 to 199.99
[%]
0.01%
Ind: 4
FS=0.00
Type: I2
P052 = 3
P051 = 40
Online
Содержание SIMOTRAS 6SG7050
Страница 8: ...Contents 01 04 0 6 Siemens AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 12: ...Safety information 01 04 1 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 30: ...Description 01 04 3 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 32: ...Shipment unpacking 01 04 4 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 46: ...Installation 01 04 5 14 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 142: ...Start up 01 04 7 56 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 298: ...Function diagrams 01 04 8 156 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 330: ...Function descriptions 01 04 9 32 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 348: ...Faults alarms 01 04 10 18 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 510: ...Parameter list 01 04 11 162 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 570: ...Connectors and binectors 01 04 12 60 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 580: ...Maintenance 01 04 13 10 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 586: ...Servicing Spare parts 01 04 14 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 590: ...Environmental compatibility 01 04 16 2 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 600: ...Appendix 01 04 18 4 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 602: ...Appendix 01 04 18 6 SIEMENS AG 6SG7000 0BA76 SIMOTRAS HD Operating Instructions ...
Страница 603: ......