BR 1
X3
X4
X1
X2
BR 2
S1
off
on
BR 3
4 3 2 1
4 3 2 1
4 3 2 1
Used in ER 701-2, ER 701-3
Setting the address area
The address area of the S5 I/O modules is set on the IM 314. This setting applies only for the
digital and analog I/O modules.
The address areas P, Q, IM3, and IM4 are available. Set the switch to the relevant position to
address the digital and analog I/O modules in these areas.
Table 7-6
Settings address areas on the IM 314
I/O area address
Switch position
O = OFF, 1 = ON
The first two switches on the left are
not relevant.
OFF
ON
P area: F000 - F0FF
S1:
0000 *
Q area: F100 - F1FF
0001
IM3 area: FC00 - FCFF
1100
IM4 area: FD00 - FDFF
1101
* Factory state
S5 interface IM 463-2
7.5 Setting the operating modes of the IM 314
S7-400 Automation System Module Data
354
Reference Manual, Ausgabe 11/2016, A5E00850736-08