Fuse
Included in this fan subassembly are standard cartridge fuse links, 5 x 20 mm, conforming to
DIN
● 1.0 AT for 24 V
The fuse is already installed on shipping from the factory.
Shielding clamps
If you do not require the shielding clamps supplied, do not install them in the fan subassembly.
Installation
Follow to the general installation guidelines when mounting the 24 V DC fan subassembly,
see
Installation manual.
Technical specifications
Dimensions, weights
Dimensions W x H x D (mm)
Weight
482.5x 109.5 x 235
Approx. 1600 g
Cable cross-section
0.5 to 2.5 mm² (litz with connector sleeve)
Electrical parameters
Lifespan of the fans at 40 °C
Typ. 70 000 h
Maximum contact load of relay contacts 1 to 6
● Switching voltage
24 VDC
● Permitted range
Static 20.4 to 28.8 VDC
Dynamic: 18.5 to 30.2 VDC
● Switching current
200 mA
Voltages, currents, electrical potentials
Input voltage
● Nominal value
24 VDC
● Permissible range
Static: 19.2 to 28 V
Rated current
450 mA
Starting current
0.9 A at 24 V
Fuses Wickmann Series 195
250 V / 1.0 AT
Power consumption
● With fan
12 W
● Without fan
1.4 W
Cable duct and fan subassemblies
9.5 The 24 V DC fan subassembly (6ES7408-1TA01-0XA0)
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
385