● For "0" signal (residual current)
Maximum 2.6 mA
Output delay (with resistive load)
● For "0" to "1"
Maximum 1 ms
● For "1" to "0"
Maximum 1 AC cycle
Minimum load current
10 mA
Zero crossing
No zero crossing switch
Size of motor starter
Maximum 5 pursuant to NEMA
Lamp load
Maximum 50 W
Connection of 2 outputs in parallel
● For redundant control of a load
Possible (only outputs connected to same
load)
Control of a digital input
Possible
Switching frequency
● With resistive load
Maximum 10 Hz
● With an inductive load in accordance with IEC
947-5-1, AC 15
Maximum 0.5 Hz
● With lamp load
1 Hz
Short-circuit protection for output
Fuse, 8 A, 250 V (per group)
● Current required for safety shutdown
At least 100 A
● Response time
Maximum 100 ms
Spare fuses
Fuse, 8 A, quick-response
● Wickmann
194-1800-0
● Schurter
SP001.1013
● Littelfuse
217.008
Changing the fuse
Note
Injury is possible.
If you change a fuse without first unplugging the front connector of the module, you may receive
an electric shock.
Always remove the front connector before changing a fuse.
Digital modules
4.19 Digital output module SM 422; DO 16 x AC 120/230 V/2 A (6ES7422-1FF00-0AA0)
S7-400 Automation System Module Data
152
Reference Manual, Ausgabe 11/2016, A5E00850736-08