Table 5-32
Unipolar output ranges
Units
Output
value in
%
Data word
Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
≧3251
2
0 %
0
1
1
1
1
1
1
1
x
x
x
x
x
x
x
x
Overflow
32511 117,589
0
1
1
1
1
1
1
0
1
1
1
1
1
1
1
1
Overshoot
range
27649 ≧100,004 0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1
27648 100,000
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
0
Nominal
range
1 0,003617 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0 0,000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 1 0,000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Limited to
the low limit
of the nomi‐
nal range, 0
V or 0 mA
- 32512
1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
≤
32513
0 %
1
0
0
0
0
0
0
0
x
x
x
x
x
x
x
x
Underflow
Table 5-33
Life-zero input ranges
Units Output
value in
%
Data word
Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
≧3251
2
0 %
0
1
1
1
1
1
1
1
x
x
x
x
x
x
x
x
Overflow
32511 117,589
0
1
1
1
1
1
1
0
1
1
1
1
1
1
1
1
Overshoot
range
27649 ≧100,004 0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
1
27648 100,000
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
0
Nominal
range
1 0,003617 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0 0,000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
- 1 -0,00361
7
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Undershoot
range
- 6912 -25,000
1
1
1
0
0
1
0
1
0
0
0
0
0
0
0
0
- 6913
-25,000
1
1
1
0
0
1
0
0
1
1
1
1
1
1
1
1
Limited to
overshoot
range lower
limit 0 V and
0 mA
- 32512
1
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
≤-3251
3
- 25 %
1
0
0
0
0
0
0
0
x
x
x
x
x
x
x
x
Underflow
Analog modules
5.4 Representation of analog values
S7-400 Automation System Module Data
186
Reference Manual, Ausgabe 11/2016, A5E00850736-08