WARNING
Installation Instructions according cULus
WARNING – Explosion Hazard - Do not disconnect while circuit is live unless area is known
to be non-hazardous.
WARNING – Explosion Hazard - Substitution of components may impair suitability for Class
I, Division 2 or Class I, Zone 2
This equipment is suitable for use in Class I, Division 2, Groups A, B, C or D; Class I, Zone
2, Group IIC, or non-hazardous locations only.
CuULu requirements for hazardous location on the battery power supply for CPUs
The backup voltage for a CPU must be supplied over a non-incendive plug connection. The
figure below shows such a plug connection.
1
2
(1)
Battery or supply voltage
(2)
CPU with "Ext. Batt." connector
Figure 1-1
Back-up voltage supply
The following conditions apply to the performance characteristics of this connection:
Voc (no load voltage) = 15 V
Vmax = 15 V
Isc (short-circuit current)= 50 mA
Imax = 50 mA
Ca = Battery/voltage supply capacity
Ci = 25 nF maximum
La = Battery/voltage supply inductance
Li = 2 mH maximum
The battery/power supply that powers the non-incendive connection must comply with the
following ratings:
Battery/Power supply
CPU input "Ext. Batt." with cable
Voc
≤
Vmax (15 V)
Isc
≤
Imax (50 mA)
Ca
≥
Ci + Cc (25 nF + Cc)
La
≥
Li + Lc (2 mH + Lc)
Cc = Cable capacity
Lc = Cable inductance
Note
If you do not know the capacity and inductance of the cable, you can use the following values:
Cc = 197 pF/m (60 pF/ft.), Lc = 0.66 mH/m (0.2 mH/ft)
General specifications
1.1 Standards, certificates and approvals
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08
17