Connecting non-isolated sensors
Depending on local conditions or interference, potential differences U
CM
(static or dynamic)
can occur between the locally distributed measuring points. If the permitted value for U
CM
is
exceeded, there must be equipotential bonding conductors between the measuring points.
1
2
3
M+
M-
U
ISO
M+
M-
M
ANA
U
CM
Figure 5-6
Connecting non-isolated sensors to an isolated AI
(1)
Non-isolated sensors
(2)
Chassis ground
(3)
Equipotential bonding conductor
M +:
Measuring line (positive)
M -:
Measuring line (negative)
M
ANA
:
Reference potential of the analog measuring circuit
U
ISO
:
Potential difference between M
ANA
and chassis ground
Note
Do not use non-isolated 2-wire transducers and non-isolated resistance-type sensors!
Analog modules
5.9 Connecting sensors to analog inputs
S7-400 Automation System Module Data
206
Reference Manual, Ausgabe 11/2016, A5E00850736-08