4.17.2
Assigning parameters to the SM 422; DO 32 x DC 24 V/0.5 A
Parameter assignment
You will find a description of the general procedure for assigning parameters to digital modules
in the respective sections.
Parameters of SM 422; DO 32 x DC 24 V/0.5 A
You will find an overview of the parameters that you can set and their default settings for the
SM 422; DO 32 x DC 24 V/0.5 A in the table below.
Table 4-13
Parameters of SM 422; DO 32 x DC 24 V/0.5 A
Parameters
Value range
Default
2
Parameter type
Scope
Enable
● Diagnostic interrupt
1
Yes/no
No
Dynamic
Module
● Destination CPU for interrupt
1 to 4
-
Static
Module
Reaction to CPU STOP
Set substitution val‐
ue (SSV)
Keep last value
(KLV)
SV
Dynamic
Module
Diagnostics
● Wire break
Yes/no
No
Static
Channel
● No load voltage L+/sensor supply
Yes/no
No
Channel group
● Short-circuit to M
Yes/no
No
Channel
● Short-circuit to L+
Yes/no
No
Channel
Set substitution value "1"
Yes/no
No
Dynamic
Channel
1
If you use the module in ER-1/ER-2, you must set this parameter to "No" because the interrupt lines are not available in
ER-1/ER-2.
2
Only in the CR (central rack) is it possible to start up the digital modules with the default settings.
See also
Digital modules
4.17 Digital output module SM 422; DO 32 x DC 24 V/0.5 A (6ES7422-7BL00-0AB0)