5.4.5
Representation of analog values in the current measuring ranges
Table 5-12
Representation of analog values in the ±3.2 mA to ±20 mA current measuring ranges
System
Current measuring range
Dec.
Hex.
± 20 mA
± 10 mA
± 5 mA
± 3.2 mA
118,515 % 32767
7FFF
23.70 mA
11.85 mA
5.93 mA
3.79 mA
Overflow
117,593 % 32512
7F00
117,589 % 32511
7EFF
23.52 mA
11.76 mA
5.88 mA
3.76 mA
Overshoot
range
27649
6C01
100,000 % 27648
6C00
20 mA
10 mA
5 mA
3.2 mA
Nominal range
75 % 20736
5100
15 mA
7.5 mA
3.75 mA
2.4 mA
0,003617 % 1
1
723.4 nA
361.7 nA
180.8 nA
115.7 nA
0 % 0
0
0 mA
0 mA
0 mA
0 mA
- 1
FFFF
- 75 % - 20736
AF00
- 15 mA
- 7.5 mA
- 3.75 mA
- 2.4 mA
- 100,000 % - 27648
9400
- 20 mA
- 10 mA
- 5 mA
- 3.2 mA
- 27649
93FF
Undershoot
range
- 117,593 % - 32512
8100
- 23.52 mA
- 11.76 mA
- 5.88 mA
- 3.76 mA
- 117,596 % - 32513
80FF
Underflow
- 118,519 % - 32768
8000
- 23.70 mA
- 11.85 mA
- 5.93 mA
- 3.79 mA
Table 5-13
Representation of analog values in current measuring ranges 0 to 20 mA
System
Current measuring range
Dec.
Hex.
0 to 20 mA
118,515 % 32767
7FFF
23.70 mA
Overflow
117,593 % 32512
7F00
117,589 % 32511
7EFF
23.52 mA
Overshoot range
27649
6C01
Nominal range
100,000 % 27648
6C00
20 mA
75 % 20736
5100
15 mA
0,003617 % 1
1
723.4 nA
0 % 0
0
0 mA
- 1
FFFF
Undershoot range
- 17,593 % - 4864
ED00
- 3.52 mA
- 4865
ECFF
Underflow
≤ - 17,596 % - 32768
8000
Analog modules
5.4 Representation of analog values
S7-400 Automation System Module Data
174
Reference Manual, Ausgabe 11/2016, A5E00850736-08