R
T
R
T
PROFIBUS DP
Transmitter
Transmitter
Transmitter
Receiver
Receiver
Receiver
Grip
Figure 8-6
Inserting the fiber-optic cables into the IM 467 FO
Bending radius for the fiber-optic cable
When placing the fiber-optic duplex core into the plug adapter and routing the cable, be sure
not to exceed the permissible bending radius of 30 mm. See also the installation guidelines
on fiber-optic cables in the SIMATIC NET PROFIBUS Networks manual.
8.4
Specifications
8.4.1
Specifications of the IM 467 (6ES7467-5GJ02-0AB0))
Dimensions and weight
Dimensions W x H x D (mm)
Weight
25 x 290 x 210
700 g
PROFIBUS DP
● Standard
PROFIBUS DP, EN 50 170
● Transmission rate
9.6 Kbps to 12 Mbps, configurable in
steps
● Transmission technology
RS 485 via 9-pin sub D socket
Current consumption
Current consumption from the S7-400 bus (24 VDC)
The IM does not consume any current at 24 V, and it only makes
this voltage available at the MPI/DP interface.
Total current consumption of the com‐
ponents connected to the DP interfa‐
ces, with a maximum of 150 mA
PROFIBUS DP
Operating conditions
Can be used in
SIMATIC S7-400, max. 4 IM 467 in
the central rack
PROFIBUS DP master interface IM 467/IM 467 FO
8.4 Specifications
S7-400 Automation System Module Data
374
Reference Manual, Ausgabe 11/2016, A5E00850736-08