5.26.3
Output ranges of the SM 432; AO 8 x 13 Bit
Configuration of analog output circuits
You can configure the outputs for operation as voltage or current outputs, or disable these.
You configure the output circuits at the "output type" parameter in
STEP 7.
Unused channels
To make sure that unused output channels of SM 432; AO 8 x 13 Bit are de-energized, set the
"Output type" parameter to "deactivated" and leave the terminal open.
Output ranges
You program the output ranges for voltage and current outputs in
STEP 7.
Table 5-75
Output ranges of the SM 432; AO 8 x 13 Bit
Selected type of output
Output range
Description
Voltage
1 V to 5 V
0 V to 10 V
± 10 V
The digitized analog values are listed in
the section "Representation of analog
values for analog output channels" in
the voltage or current output range.
Current
0 to 20 mA
4 to 20 mA
± 20 mA
Default
The output type "Voltage" and output range "± 10 V" are set by default at the module. You can
always use this combination of output type and range without having to program the SM 432;
AO 8 x 13 Bit in
STEP 7.
Analog modules
5.26 Analog output module SM 432; AO 8 x 13 Bit (6ES7432-1HF00-0AB0)
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08