Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
98
Installation and Operating Manual, 01/2010, A5E00085586-10
Assignable parameters for application 6
Table 8- 7
Parameters for application 6 of SM 326; DI 24 x DC 24V
Parameters
Range of values in safety mode
Type
Effective range
"Parameters" tab
Mode of operation
Safety mode
Static
Module
F parameter:
F monitoring time
10 ms to 10000 ms
Static
Module
Module parameters:
Diagnostic interrupt
activated/deactivated
Static
Module
Module parameters for a power supply group:
Internal sensor supply
of the module
activated/deactivated
Static
Power supply group
Short-circuit test
activated/deactivated * (only if "Sensor
Supply via Module" is activated)
Static
Power supply group
For single channels or channel pairs:
activated
activated/deactivated
Static
Channel pair
Evaluation of the
sensors
1oo2 evaluation
Static
Channel pair
Type of sensor
interconnection
Two-channel, equivalent
Two-channel, nonequivalent
Single-channel
Static
Channel pair
Discrepancy behavior
(only two-channel)
"Provide last valid value"
Provide 0 value
Static
Channel pair
Discrepancy time
10 ms to 30000 ms (only for two-
channel)
Static
Channel pair
"Redundancy" tab
Redundancy
2 modules
Static
Module
Redundant module
(selection of an existing additional
module of the same type)
Static
redundant module
pair
Discrepancy time
10 ms to 30000 ms
Static
redundant module
pair
* Vs does not clock, if the short-circuit test is deactivated.
Содержание Simatic S7-300
Страница 326: ...Response times D 1 Response Times Fail safe signal modules 326 Installation and Operating Manual 01 2010 A5E00085586 10 ...
Страница 344: ...Glossary Fail safe signal modules 344 Installation and Operating Manual 01 2010 A5E00085586 10 ...
Страница 356: ...Product Information 4 A5E03004206 01 ...