Digital modules
8.3 SM 326; DI 24 x DC 24V
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
85
Wiring scheme for application 2 with single-channel connection of two redundant sensors
Two redundant sensors are wired to a single channel at the two analog modules for each
process signal. The sensors can also be connected to an external sensor supply.
/
0
',
9V
/
0
',
9V
60
',['&9
60
',['&9
$FTXLVLWLRQRIWKHVDPH
SURFHVVYDULDEOHZLWK
PHFKDQLFDOO\VHSDUDWH
VHQVRUV
Figure 8-9
Wiring scheme of the SM 326; DI 24 x DC 24V for application 2 – two redundant sensors
single-channel connection
Assignable parameters for application 2
Table 8- 3
Parameters for application 2 of SM 326; DI 24 x DC 24V
Parameters
Range of values in standard mode
Type
Effective range
"Parameters" tab
Mode of operation
Standard mode
static
module
Module parameters:
Diagnostic interrupt
activated/deactivated
static
module
Module parameters for a power supply group:
Internal sensor supply
of the module
deactivated (for single-channel
connection of a sensor)
activated/deactivated
(for redundant sensor)
static
Power supply group
Short-circuit test
activated/deactivated * (only if "Sensor
Supply via Module" is activated)
static
Power supply group
For single channels or channel pairs:
activated
activated/deactivated
static
channel
"Redundancy" tab **
Redundancy
2 modules
static
module
Redundant module
(selection of an existing additional
module of the same type)
static
redundant module
pair
Discrepancy time
10 ms to 30000 ms
static
redundant module
pair