Safety protector
10.3 Configuration Variants
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
299
10.3
Configuration Variants
Introduction
The module supports two variants with safety protector, depending on whether or not it is
required to hot-swap a module.
Special features when using CPU 31xF-2 DP and CPU 31xF-2 PN/DP
Note the following special features with central or distributed operation of CPU 31xF-2 DP
and CPU 31xF-2 PN/DP:
●
The F-CPU reaches the limits for
surge resistance specified in the technical data using
the overvoltage protection components specified in the installation manual
(
operation.
●
If you operate a structure that does not require protective elements, either if surge
protection is not required for your structure or if you have implemented other safety
measures, you can create an
ungrounded structure.
Configuration of S7-300/ET 200M with safety protector (no hot-swapping)
The safety protector increases the width of S7-300/ET 200M by 40 mm. This setup still
permits installation of eight to twelve signal modules.
The example below shows a configuration with seven signal modules.
1
2
3
4
5
①
Power supply
②
IM 153-2
③
Standard signal modules
④
Safety protector
⑤
Fail-safe signal modules
Figure 10-3 Configuration of ET 200M with safety protector (hot-swapping of the module not