Digital modules
8.6 SM 326; DO 10 x DC 24V/2A (6ES7326-2BF01-0AB0)
Fail-safe signal modules
148
Installation and Operating Manual, 01/2010, A5E00085586-10
Assignable parameters for applications 1, 3 and 5
Table 8- 19 Parameters of the SM 326; DO 10 x DC 24V/2A for applications 1, 3 and 5
Range of values
Parameters
Safety mode
Standard mode
Type
Effective
range
"Outputs" tab
Enable diagnostic
interrupt
Activated/deactivated
Activated/deactivated
Static
Module
Mode
Safety mode
according to SIL 2
Safety mode
according to SIL 3
Standard mode
Static
Module
Monitoring time
10 ms to 10000 ms
—
Static
Module
Disable light test
Activated/deactivated
Activated/deactivated
Static
Module
Reaction during
CPU STOP
—
Switch to fail-safe
value
Keep last valid
value
Static
Module
Group diagnostics
Activated/deactivated
Activated/deactivated
Static
Channel
Switch to fail-safe
value "1"
—
Activated/deactivated
Static
Channel
"Redundancy" tab
Redundancy
none
—
Static
Module
Содержание Simatic S7-300
Страница 326: ...Response times D 1 Response Times Fail safe signal modules 326 Installation and Operating Manual 01 2010 A5E00085586 10 ...