General technical data
7.5 Mechanical and Climatic Environmental Conditions
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
69
Mechanical environmental conditions
The mechanical environmental conditions for the operation of fail-safe signal modules are
defined in the table below based on sinusoidal vibration.
Frequency range (Hz)
Continuous
Intermittent
10 ≤ f ≤ 58
Amplitude = 0.0375 mm
Amplitude = 0.075 mm
58 ≤ f ≤ 150
Constant acceleration = 0.5 g
Constant acceleration = 1 g
Reducing vibration
Suitable measures must be taken to reduce acceleration and amplitude at locations where
the fail-safe signal modules are exposed to greater shock or vibration.
It is advisable to install the modules on a damping material such as rubber-to-metal vibration
dampers.
Test of mechanical environmental conditions
The table defines the type and scope of testing mechanical environmental conditions.
Test of ...
Test standard
Comments
Vibration
Vibration test to IEC 68
Part 2-6 (sinusoidal)
Type of vibration: Frequency cycles at a rate of change
of 1 octave/minute.
5 Hz ≤ f ≤ 9 Hz, constant Amplitude 0.075 mm
9 Hz ≤ f ≤ 150 Hz, constant Acceleration 1 g
Duration of vibration: 10 frequency cycles per axis at
each one of the three perpendicular axes
Shock
Shock test to IEC 68
Part 2-27
Type of shock: Half sine
Severity of shock: 15 g peak value, duration 11 ms
Direction of shock: Three shocks in +/- direction at each
of the three perpendicular axes