Digital modules
8.7 SM 326; F-DO 10 x DC 24V/2A PP (6ES7326-2BF10-0AB0)
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
179
Technical data
Electrical isolation
Between channels and backplane bus
Yes
Between channels and the power supply of the
electronics
Yes
Between channels
In groups of
Yes
5
Permitted potential difference
Between different circuits
75 V DC
60 V AC
Insulation test voltage
370 V AC for 1 min.
Current consumption
From backplane bus
100 mA, maximum
From supply voltage 1L+
100 mA, maximum
From load voltage 2L+/ 3L+ (no-load)
100 mA, maximum
Power loss of the module
6 W, typical
Status, Interrupts, Diagnostics
Status display
1 green LED
1 red LED
Interrupts
Diagnostic interrupt
Programmable
Diagnostics functions
Programmable
Group fault display
Red LED (SF)
Fail-safe mode display
Green LED (SAFE)
Diagnostic information can be read out
Possible
Fail-safe values
Switch to / Keep last valid value
Actuator selection data
Output voltage
For "1" signal
Minimum L+ (-1.0 V)
Output current
For "1" signal
–
Rated value
–
Approved range
2 A
7 mA to 2.4 A
For "0" signal (residual current)
0.5 mA, maximum
Load resistance range
Up to 40 °C
12 Ω to 3.4 kΩ
Up to 60 °C
12 Ω to 3.4 kΩ
Lamp load
5 W, maximum
Parallel switching of 2 outputs
For redundant load control
With assigned redundancy
For power increase
Not possible
Control of a digital input
Possible
Содержание Simatic S7-300
Страница 326: ...Response times D 1 Response Times Fail safe signal modules 326 Installation and Operating Manual 01 2010 A5E00085586 10 ...
Страница 344: ...Glossary Fail safe signal modules 344 Installation and Operating Manual 01 2010 A5E00085586 10 ...