Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
Installation and Operating Manual, 01/2010, A5E00085586-10
245
Assignable parameters for application 4
Table 9- 18 Parameters for application 4 of SM 336; F-AI 6 x 0/4 ... 20 mA HART
Parameters
Range of values in safety mode
Type
Effective range
Diagnostic interrupt
Activated/deactivated
Static
Module
Behavior after channel
fault
Passivate the entire
module/Passivate the channel
Static
Module
HART_Gate
Off/On/Can be switched
Static
Module
Interference frequency
suppression
50 Hz/60 Hz
Static
Module
Evaluation of the
sensors
1oo1 evaluation
Static
Channel
Measuring range
4 to 20 mA, 0 to 20 mA
Static
Channel
F-wire break detection activated/deactivated
(in the 4 to 20 mA measuring range)
Static
Channel
Smoothing
1 / 4 / 16 / 64 conversion cycles
Static
Channel
HART function
Activated/deactivated
Static
Channel
HART repetitions
0 to 255
Static
Channel
HART group
diagnostics
Activated/deactivated
Static
Channel
Redundancy
Activated/deactivated
Static
Channel