Digital modules
8.4 SM 326; DI 8 x NAMUR
Fail-safe signal modules
120
Installation and Operating Manual, 01/2010, A5E00085586-10
Assignable parameters for application 6
Table 8- 13 Parameters for application 6 of SM 326; DI 8 x NAMUR
Parameters
Range of values in safety mode
Type
Effective range
"Inputs" tab
Enable diagnostic
interrupt
Activated/deactivated
Static
Module
Safety mode
Activated
Static
Module
Monitoring time
10 ms to 10000 ms
Static
Module
Sensor evaluation
1oo2 evaluation
Static
Module
Group diagnostics
Activated/deactivated
Static
channel
Discrepancy time
10 ms to 30000 ms
Static
channel
"Redundancy" tab
Redundancy
2 modules
Static
Module
Redundant module
(selection of an existing
additional module of the same
type)
Static
redundant module
pair
Discrepancy time
10 ms to 30000 ms
Static
redundant module
pair