Analog modules
9.3 SM 336; F-AI 6 x 0/4 ... 20 mA HART
Fail-safe signal modules
260
Installation and Operating Manual, 01/2010, A5E00085586-10
Diagnostic message
Possible causes of the problem
Corrective measures
Excessive electromagnetic interference
at times
Eliminate the interference, and
Switch the supply voltage of the F-
CPU/IM OFF/ON,
Remove/insert F-SM, or
Switch external auxiliary voltage of F-
SM OFF/ON
Defective module
Replace the module
EPROM error
RAM error
Inconsistent firmware
Repeat firmware update
Internal error during analog value test
Replace the module
ADC/DAC error
Impermissible U
CM
Eliminate the interference, and
Switch the supply voltage of the F-
CPU/IM OFF/ON,
Remove/insert F-SM, or
Switch external auxiliary voltage of F-
SM OFF/ON
Firmware update successfully
performed
—
—
Firmware is faulty
CRC error
Switch the supply voltage of the F-
CPU/IM OFF/ON,
Remove/insert F-SM, or
Switch external auxiliary voltage of F-
SM OFF/ON
Then, repeat the firmware update.
Firmware update error
Defective module
Replace the module
Firmware is faulty
Firmware update was canceled
Repeat the firmware update.
Firmware version inconsistent
Supply voltage of module is missing
Connect the module to the supply
voltage, and repeat the firmware update.
Discrepancy error
Assigned tolerance window exceeded on
expiration of the discrepancy time
Extend the tolerance window and/or
discrepancy window
Wiring incorrect
Check wiring, and
Switch the supply voltage of the F-
CPU/IM OFF/ON,
Remove/insert F-SM, or
Switch external auxiliary voltage of F-
SM OFF/ON
Applied external voltage
Remove the external voltage effect, and
Switch the supply voltage of the F-
CPU/IM OFF/ON,
Remove/insert F-SM, or
Switch external auxiliary voltage of F-
SM OFF/ON
Short-circuit
(short-circuit to L+ of sensor
supply, ground short-circuit or
defective sensor supply)
Defective module
Replace the module
Interruption of the measuring lead
between the module and sensor
Restore the cable connection
Wire break
Incorrect measuring range setting
Check the measuring range setting