Diagnostics with the CP 341
8.1 Diagnostics Functions of the CP 341
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
196
Manual, 09/2008, A5E02191071-01
Event class 8 (08H):
"Receive error"
Event no.
Event
Remedy
(08)15H
Discrepancy between settings for transmission
attempts of the CP and the communication partner.
Set the same number of transmission attempts for
the communication partner as for the CP. Check for
malfunction on partner device, possibly by using an
interface test device interconnected in the data link.
(08)16H
•
The length of a received message frame
exceeded the maximum specified length.
Correction at the partner is necessary.
(08)18H
ASCII driver only:
DSR = OFF or CTS = OFF
The partner has switched the DSR or CTS signal to
"OFF" before or during a transmission.
Check the partner's control of the RS 232C
accompanying signals.
Event class 9 (09H):
"Response message frame received from interconnection partner with errors or error message frame"
Event no.
Event text
Remedy
(09)02H
Only for RK 512:
Memory access error in partner (memory does not
exist)
With SIMATIC S5 as partner:
•
Incorrect area for indicator word, or
•
Data area does not exist (except DB/DX), or
•
Data area too short (except DB/DX)
Check that the partner has the desired data area and
that it is big enough, or check the parameters of the
called system function block.
Check the length specified in the system function
block.
(09)03H
Only for RK 512:
DB/DX access error in the partner (DB/DX does
not exist or is too short)
With SIMATIC S5 as partner:
•
DB/DX does not exist, or
•
DB/DX too short, or
•
DB/DX number impermissible
Permissible source area exceeded with FETCH
request
Check that the partner has the desired data area and
that it is big enough, or check the parameters of the
called system function block.
Check the length specified in the system function
block.
(09)04H
Only for RK 512:
Partner reports "Illegal request type".
Partner malfunction, because the CP never outputs
a system command.
(09)05H
RK 512 only:Partner error or SIMATIC S5 partner
error:
•
Source/destination type not permissible, or
•
Memory error in partner programmable
controller, or
•
Error notifying CP/CPU at the partner, or
•
Partner programmable controller is in STOP
mode
Check if the partner can transmit the desired data
type.
Check the configuration of the partner hardware.
Set the mode selector switch of the partner
programmable controller to RUN.