Diagnostics with the CP 341
8.1 Diagnostics Functions of the CP 341
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
190
Manual, 09/2008, A5E02191071-01
Event Class 4 (04H):
"CP detected error in data traffic CP - CPU"
Event no.
Event text
Remedy
(04)0AH
An error has occurred during data transmission
between the CPU and CP. The data
transmission was canceled due to a RESET,
because:
•
Destination DB is not available
•
Destination DB is too short
•
RESET bit set at FB
Create destination DB in the user program or increase
the length of the existing destination DB.
Event class 5 (05H):
"Error while processing CPU request"
Event no.
Event
Remedy
(05)01H
Current request canceled as a result of CP restart. No remedy is possible in the case of a POWER ON.
In the case of parameter reassignment of the CP by
the programming device, before writing an interface
you should ensure there are no more requests
running from the CPU.
(05)02H
Request is not permitted in this CP operating mode
(e.g., device interface parameters not assigned).
Assign parameters for the device interface.
(05)05H
Printer driver only:
System data block with message texts not
available on the CP
Use the parameter assignment software to configure
the message texts, and then carry out a complete
restart.
(05)06H
Printer driver only:
Message text not available
Use the parameter assignment software to configure
the message texts, and then carry out a complete
restart.
(05)07H
Printer driver only:
Message text too long
Edit the message text to reduce it to a length of
fewer than 150 characters (or no more than 250
characters if it contains variables)
(05)08H
Printer driver only:
Too many conversion statements
You have configured more conversion statements
than variables. Conversion statements without
associated variables will be ignored.
(05)09H
Printer driver only:
Too many variables
You have configured more variables than conversion
statements. Variables without associated conversion
statements will not be output.
(05)0AH
Printer driver only:
Unknown conversion statement
Check the conversion statement. Undefined or
unsupported conversion statements are replaced in
the printout with ******.
(05)0BH
Printer driver only:
Unknown control statement
Check the control statement. Undefined or
unsupported control statements will be ignored. The
control statement will not be output as text either.
(05)0CH
Printer driver only:
Conversion statement not executable
Check the conversion statement. Conversion
statements that cannot be executed are output in the
printout in accordance with the defined width and the
valid remainder of the conversion statement or the
default display is output with "*" characters.
长沙工控帮教育科技有限公司
www.gkbpx.com