Communication via Function Blocks
6.3 Using the Function Blocks with the 3964(R) Procedure
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
138
Manual, 09/2008, A5E02191071-01
FB P_RCV_RK parameters
The table below lists the parameters of the FB P_RCV_RK.
Note
The L_TYP, L_NO, L_OFFSET, L_CF_BYT, and L_CF_BIT parameters are irrelevant for the
3964(R) procedure and do not have to be assigned.
Table 6- 3
FB P_RCV_RK parameters
Name
Sort
Data type
Comment
Permitted values, remark
EN_R
INPUT
BOOL
Enables data reading
R
INPUT
BOOL
Cancels request
Cancels the request in progress. Receiving is
disabled.
LADDR
INPUT
INT
CP 341 start address
The start address is taken from STEP 7.
DB_NO
INPUT
INT
Data block number
Receive DB No.:
CPU-specific, zero is not allowed
DBB_NO
INPUT
INT
Data byte number
0 ≤ DBB_NO ≤ 8190 Receive data starting
from data byte
NDR
OUTPUT
BOOL
Request completed without
errors, data accepted
STATUS parameter == 16#00;
ERROR
1
OUTPUT
BOOL
Request completed with
errors
Error information is written to the STATUS
parameter.
LEN
1
OUTPUT
INT
Length of the message
frame received
1 ≤ LEN ≤ 4096, specified in number of bytes
STATUS
1
OUTPUT
WORD
Specification of error
If ERROR == 1, the STATUS parameter will
contain error information.
1
The parameter is available until the next time the FB is called.