Basic Principles of Serial Data Transmission
2.8 Configuration data
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
Manual, 09/2008, A5E02191071-01
85
2.8.2
Configuration Data of the RK 512 Computer Connection
You can use the parameter assignment data of the RK 512 computer link to adjust the
CP 341 to suit the properties of the communication partner.
Parameter Assignment Data of the RK 512 Computer Link
The parameters are identical to those of the 3964(R) procedure because the 3964(R)
procedure is a subset of the RK 512 computer link in the ISO 7-layer reference model (see
Section "Configuration data (Page 79)").
Note
Exception: The number of data bits per character is set permanently to 8 with the RK 512
computer link.
The parameters of the transport layer (layer 4) must be specified in the function blocks (FB)
used.
Waiting time for response message frames
Table 2- 9
RK512 computer connection
Parameters
Description
Range of
values
Default value
Waiting time for response message
frames
Once the command message frame
has been transmitted, the RK 512 waits
for a response message frame from the
communication partner within the
monitoring time. The duration of the
monitoring time depends by default on
the transmission speed 20 s.
This monitoring time can be reduced by
setting parameters for the user in the
"RK512" dialog of the parameter
assignment interface.
Activate the parameter ""dependent on
transmission rate" to monitor response message
frames expected from the partner with the
following waiting times:
•
300 baud 10 s
•
600 baud 7 s
•
1200 baud 5 s
•
from 38400 baud 3 s
The "grayed" field "maximum waiting time" is
only used to display the monitoring time used
and cannot be edited!
•
Yes
•
No
No