Mounting the CP 341
4.2 Mounting and Dismounting the CP 341
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
112
Manual, 09/2008, A5E02191071-01
4.2
Mounting and Dismounting the CP 341
When installing and removing the CP 341, you must observe certain rules.
Tool
For installing and removing the CP 341, you require a 4.5 mm cylindrical screwdriver.
24 V DC load power supply
The CP 341 has an external 24 V DC load power supply. The 24 V DC load power supply
must satisfy the following requirements:
Only a safe, isolated extra-low voltage of ≤ 60 V DC may be used as the load current supply.
The reliable electrical insulation can be implemented in compliance with the requirements of
●
VDE 0100 Part 410 / HD 384–4–41 / IEC 364–4–41
(as functional extra-low voltage with safe electrical isolation) or
●
VDE 0805 / EN 60950 / IEC 950
(as safety extra-low voltage SELV) or VDE 0106 Part 101.
4.2.1
Installation steps
Inserting the rack (mounting rail)
To insert the CP 341 in a rack (mounting rail), proceed as follows:
1. Switch the CPU to STOP mode.
2. Switch off the power supply.
3. The CP 341 is accompanied by an expansion bus. Plug this onto the backplane
connector of the module to the left of the CP 341.
4. If more modules are to be mounted to the right of the CP 341, plug the expansion bus of
the next module onto the right backplane connector of the CP 341.
5. Hook the FM 341 onto the mounting rail and swivel it downwards.
6. Screw the CP 341 tight.
7. Connect the DC 24 V of the load power supply to the CP 341.