Technical Specifications
A.1 Technical Specifications of the CP 341
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
Manual, 09/2008, A5E02191071-01
217
Table A- 8
Additional parameters of end-of-frame detection
ASCII driver with end-of-frame detection after expiration of character delay time
Parameters
No other parameter assignments need to be made. The end of a frame is
detected when the programmed character delay time elapses.
ASCII driver with end-of-frame detection using assignable end-of-text characters
Parameters
The following can be assigned:
Number of end-of-text characters: 1 or 2
Hex code for first/second end-of-text character
ASCII driver with end-of-frame detection using configured frame length
Parameters
The following can be assigned:
Message frame length: 1 to 4096 bytes
Technical specifications for the printer driver
The table below shows the technical specifications for the printer driver.
Table A- 9
Technical specifications for the printer driver
Printer driver
Length of the text SDB
15 kbytes
Parameters
The following can be assigned:
•
Transmission rate: 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600, 76800, 115200 bits/s
•
Character frame: 10 or 11 bits
•
Flow control: None, XON/XOFF, RTS/CTS
•
XON/XOFF characters (with "flow control" = "XON/XOFF" only)
•
Wait for XON after XOFF (wait time for CTS = ON): 20 ms to
655350 ms in 10 ms increments
•
Message text: max. 150 characters (max. 250 characters when
variables are displayed)
•
Left margin (number of blanks): 0 to 255
•
Lines per page (with header and footer): 1 to 255 or 0 (continuous
printing)
•
Separators/line end: CR, LF, CR LF, LF CR
•
Character set: IBM Proprinter or user-defined
•
Printer emulation for bold, condensed, expanded, and italic type and
underlining: HP Deskjet, HP Laserjet, IBM Proprinter or user-defined
•
1/2 header and/or footer
See also
Technical Specifications of the Function Blocks (Page 178)