Commissioning
9.3 Commissioning procedure
S7-1500R/H redundant system
180
System Manual, 10/2018, A5E41814787-AA
9.3
Commissioning procedure
Requirements
●
The CPUs are in the "Factory settings" state or have been reset to factory settings. You
can find more information in the section Resetting CPUs to factory settings (Page 277).
●
The CPUs have the same or compatible article numbers.
●
The SIMATIC memory cards are as delivered or have been formatted and are not write-
protected.
●
The two CPUs of the S7-1500R/H redundant system have the same function and
firmware version. You can find more information in the section Firmware update
(Page 272).
Commissioning procedure
To commission the S7-1500R/H redundant system, we recommend the following procedure:
Table 9- 1
Procedure for commissioning SIMATIC S7-1500R/H
Step
Procedure
Further information
1
Configure hardware in STEP 7
Section Configuration (Page 136)
2
Create user program
Section Programming the S7-1500R/H
(Page 148) and STEP 7 online help
3
Insert required modules
Section Installation (Page 96)
4
Wire configuration (supply voltage, PROFINET ring, redundancy con-
nections)
5
Insert SIMATIC memory cards in the CPUs
Section Removing/plugging in SIMATIC
memory cards (Page 181)
6
Switch on CPUs and system power supply
Section First power-on of the CPUs
(Page 184)
7
CPU pairing
Section CPU pairing (Page 184)
8
Assign CPUs redundancy IDs
Section Redundancy IDs (Page 187)
9
Check LEDs
You can find the meaning of the LEDs in
the module manuals.
10
Evaluate information on the CPU displays
Section CPU display (Page 248)
11
Load hardware configuration and user program to the CPUs
Section Downloading projects to the
12
Test inputs and outputs
The following functions are helpful: Moni-
toring and modifying tags, testing with
program status, forcing, and controlling
outputs in STOP. You can find more
information in the section Test functions
(Page 282).