Application planning
3.6 Hardware configuration
S7-1500R/H redundant system
System Manual, 10/2018, A5E41814787-AA
89
PROFINET devices suitable for the redundant system
The table below shows the maximum number of PROFINET devices in the redundant
system. The maximum number includes switches, S7-1500R/H CPUs, S7-1500 CPUs (V2.5
or later) and HMI devices. It does not include media converters.
Table 3- 6
Number of PROFINET devices in the redundant system
PROFINET devices
Maximum number, S7-
1500R
Maximum number,
S7-1500H
In the PROFINET ring
50 (Recommendation
16)
1)
50
In the PROFINET ring and separated with switches
(line)
66
258
1)
Recommendation: The number of devices in the PROFINET ring affects the availability of the S7-
1500R system. You should therefore operate no more than 16 PROFINET devices (including R-
CPUs) in the PROFINET ring. If you operate significantly more devices in the PROFINET ring, the
availability of the IO devices and R-CPUs is reduced.
The technical specifications in the documentation are based on the recommended maximum of 16
PROFINET devices in the ring in S7-1500R.
Содержание Simatic S7-1500H
Страница 1: ......