Commissioning
9.8 Identification and maintenance data
S7-1500R/H redundant system
242
System Manual, 10/2018, A5E41814787-AA
Reference
The description of the instructions can be found in the STEP 7 online help.
Reading I&M data from displays
Proceed as follows to read the I&M data of a CPU:
1.
Navigate to the "Overview/PLC" menu on the display of the CPU.
2.
Select "Plant designation" or "Location identifier". Click "OK" to confirm.
Reading I&M data via STEP 7
Requirement: There must be an online connection to the CPU.
Proceed as follows to read I&M data using STEP 7 from the primary and backup CPU:
1.
Select the CPU in the project tree.
2.
Go to "Online & diagnostics".
3.
In the "Diagnostics" folder, select the "General" area.
Enter maintenance data over STEP 7
STEP 7 assigns a default module name. You can enter the following information:
●
Plant designation (I&M 1)
●
Location identifier (I&M 1)
●
Installation date (I&M 2)
●
Additional information (I&M 3)
To enter maintenance data via STEP 7, follow these steps:
1.
Select the CPU in the STEP 7 device view.
2.
Go to properties, "General", and select the "Identification & Maintenance" area.
3.
Enter the data.
During the loading of the hardware configuration, the maintenance data (I&M 1, 2, 3) are
also loaded.