System overview
2.2 Configuration
S7-1500R/H redundant system
34
System Manual, 10/2018, A5E41814787-AA
Component
Function
Diagram
Synchronization mod-
ules (for S7-1500H)
You create two redundancy connections between the H-CPUs
with fiber-optic cables using a total of four synchronization
modules (two in each H-CPU).
The following synchronization module versions can be or-
dered:
•
Sync module 1 GB FO 10 m: for fiber-optic cables up to
10 m in length
•
Sync module 1 GB FO 10 km: for fiber-optic cables up to
10 km in length
Fiber-optic cable (for
S7-1500H)
You connect the two synchronization modules for each CPU in
a pair with a fiber-optic cable. The following lengths of fiber-
optic cables can be ordered:
•
1 m
•
2 m
•
10 m
•
Up to 10 km (on request)
4-pin connection plug
for CPU supply volt-
age
The 4-pin connection plug provides the supply voltage.
System power supply
(PS)
The system power supply can be connected to the backplane
bus using a U connector. In the S7-1500R/H redundant sys-
tem, the system power supply does not support diagnostics.
Various models of system power supplies are available:
•
PS 25 W 24 V DC
•
PS 60 W 24/48/60 V DC
•
PS 60 W 24/48/60 V DC HF
Extended retentivity of the PS is not supported in S7-
1500R/H.
•
PS 60 W 120/230 V AC/DC
A power cable connector with coding element and U connector
is included in the scope of delivery for the system power sup-
ply and can be ordered as spare part.
Load power supply
(PM)
The load power supply (PM) supplies the system power supply
(PS) and central modules (CPU) with 24 V DC.
If you are using load power supplies, we recommend the de-
vices from our SIMATIC series. These devices can be mount-
ed on the mounting rail.
Various models of load power supply are available:
•
PM 70 W 120/230 V AC
•
PM 190 W 120/230 V AC
Содержание Simatic S7-1500H