Technical specifications
13.2 Electromagnetic compatibility
S7-1500R/H redundant system
296
System Manual, 10/2018, A5E41814787-AA
13.2
Electromagnetic compatibility
Definition
Electromagnetic compatibility (EMC) is the ability of an electrical installation to function
satisfactorily in its electromagnetic environment, without affecting that environment.
The S7-1500R/H redundant system also meets the requirements of EMC legislation for the
European Single Market. This is dependent on the S7-1500R/H redundant system complying
with the requirements and guidelines relating to electrical equipment.
EMC in accordance with NE21
The S7-1500R/H redundant system meets the EMC specifications of NAMUR guideline
NE21.
Pulse-shaped disturbances
The table below shows the electromagnetic compatibility of the S7-1500R/H redundant
system with regard to pulse-shaped disturbances.
Table 13- 1 Pulse-shaped disturbances
Pulse-shaped disturbance
Test voltage
Corresponds
with degree of
severity
Electrostatic discharge in accordance
with IEC 61000-4-2.
Air discharge: ±8 kV
Contact discharge: ±6 kV
3
3
Burst pulses (high-speed transient dis-
turbances) in accordance with
IEC 61000-4-4.
±2 kV (power supply cable)
±2 kV (signal cable > 30 m)
±1 kV (signal cable < 30 m)
3
3
High-energy single pulse (surge) in accordance with IEC 61000-4-5
External protective circuit required (not for 230 V modules)
You can find more information in the Designing interference-free controllers function
manual.
3
•
Asymmetric coupling
±2 kV (power supply cables)
DC with protective elements
±2 kV (signal/data line only > 30 m), with
protective elements
•
Symmetric coupling
±1 kV (power supply cable) DC with
protective elements
±1 kV (signal/data line only > 30 m), with
protective elements